bacnet - find-devices
Enumerate all BACnet devices and routers reachable from the current host.
Usage
iottack bacnet find-devices [OPTIONS]
Description
Sends a BACnet Who-Is broadcast (or unicast to --host) and a Who-Is-Router
broadcast to discover all BACnet devices and routers on the reachable network
segment. Unlike bacnet/scan, no property reads are performed, making this a
fast enumeration sweep.
Equivalent to BACteria find_devices().
Two discovery mechanisms run in sequence:
- Who-Is/I-Am: discovers BACnet devices; each I-Am response yields device ID, vendor, segmentation and max APDU size.
- Who-Is-Router/I-Am-Router-To-Network: discovers BACnet routers and the network numbers they route to, enabling lateral discovery of downstream segments.
Use --network to restrict the Who-Is to a specific BACnet network number routed
via the target host.
Severity mapping
| Finding | Severity |
|---|---|
| No devices or routers found | Info |
| Devices discovered | High |
| Routers discovered | High |
Options
| Flag | Short | Default | Description |
|---|---|---|---|
--host <HOST> | -H | (broadcast) | Unicast target address; omit to broadcast |
--port <PORT> | -p | 47808 | BACnet/IP UDP port |
--timeout-ms <MS> | - | 3000 | Discovery window in ms |
--network <NET> | -n | - | BACnet network number to query via router |
--output <FILE> | -o | - | Save result to a file |
--format <FORMAT> | -f | text | text or json |
--verbose | -v | - | Increase log verbosity |
Example
$ iottack bacnet find-devices
Plugin name: bacnet/find-devices
Execution time: 3.01 s
Status: pass
Date: 2025-11-08 00:00:00 UTC
3 BACnet devices found
192.168.1.50:47808 ID=1001 vendor=Siemens (16) max-apdu=1476
192.168.1.51:47808 ID=2002 vendor=Schneider Electric (11) max-apdu=1476
192.168.1.52:47808 ID=3003 vendor=Johnson Controls (5) max-apdu=480
1 BACnet router found
192.168.1.1:47808 networks=[200, 201, 202]