Keyboard shortcuts

Press ← or → to navigate between chapters

Press S or / to search in the book

Press ? to show this help

Press Esc to hide this help

bacnet - info

Show basic identification and status properties of a BACnet/IP device.

Usage

iottack bacnet info --host <HOST> [OPTIONS]

Description

Connects to the target BACnet/IP device and reads a curated set of Device-object properties that identify and characterize the device:

  • vendor
  • model
  • firmware version
  • application software version
  • location
  • protocol version
  • APDU transport settings
  • system status
  • local clock
  • backup/restore state

All reads are unauthenticated ReadProperty requests on the Device object. Any identifying property returned without credentials is flagged Critical.

Properties read

PropertyDescription
Object IdentifierDevice object ID (type=8, instance=N)
Object NameHuman-readable device name
System StatusOperational status (operational, load-expected, etc.)
Vendor NameManufacturer string
Vendor IdentifierNumeric vendor ID
Model NameDevice model
Firmware RevisionFirmware version string
Application Software VersionApplication layer software version
DescriptionFree-text description
LocationPhysical or logical location
Protocol VersionBACnet protocol version
Protocol RevisionBACnet protocol revision
Max APDU Length AcceptedMaximum APDU size in bytes
Segmentation SupportedSegmentation capability
APDU TimeoutPer-request timeout in milliseconds
APDU RetriesNumber of APDU retries
Database RevisionConfiguration database revision counter
Last Restart ReasonReason for last device restart
Backup and Restore StateBackup/restore operational state
Local DateDevice local date
Local TimeDevice local time
UTC OffsetUTC offset in minutes
Daylight SavingsDaylight savings status
Profile NameBACnet interoperability profile

Severity mapping

FindingSeverity
Device responds but no properties readableHigh
Identifying properties readable unauthenticatedCritical

Options

FlagShortDefaultDescription
--host <HOST>-H(required)Target BACnet/IP device
--port <PORT>-p47808BACnet/IP UDP port
--timeout-ms <MS>-5000Per-request timeout in ms
--output <FILE>-o-Save result to a file
--format <FORMAT>-ftexttext or json
--verbose-v-Increase log verbosity

Example

$ iottack bacnet info --host 192.168.1.50

Plugin name:    bacnet/info
Execution time: 2.31 s
Status:         pass
Date:           2025-11-05 00:00:00 UTC

18 device properties readable unauthenticated at 192.168.1.50:47808
  Address:    192.168.1.50:47808
  Device ID:  1001
  Vendor ID:  16 (Siemens)
  Max APDU:   1476
  Object Identifier: Device:1001
  Object Name: HVAC-Controller-01
  System Status: 0
  Vendor Name: Siemens
  Model Name: PXC100.D
  Firmware Revision: 2.4.1
  Application Software Version: 3.1.0
  Description: Building 7, HVAC Zone A
  Location: Level 3, Plant Room
  Protocol Version: 1
  Protocol Revision: 14
  Local Date: 2025-11-05
  Local Time: 09:42:15.00
  UTC Offset (min): -300