bacnet - info
Show basic identification and status properties of a BACnet/IP device.
Usage
iottack bacnet info --host <HOST> [OPTIONS]
Description
Connects to the target BACnet/IP device and reads a curated set of Device-object properties that identify and characterize the device:
- vendor
- model
- firmware version
- application software version
- location
- protocol version
- APDU transport settings
- system status
- local clock
- backup/restore state
All reads are unauthenticated ReadProperty requests on the Device object. Any identifying property returned without credentials is flagged Critical.
Properties read
| Property | Description |
|---|---|
| Object Identifier | Device object ID (type=8, instance=N) |
| Object Name | Human-readable device name |
| System Status | Operational status (operational, load-expected, etc.) |
| Vendor Name | Manufacturer string |
| Vendor Identifier | Numeric vendor ID |
| Model Name | Device model |
| Firmware Revision | Firmware version string |
| Application Software Version | Application layer software version |
| Description | Free-text description |
| Location | Physical or logical location |
| Protocol Version | BACnet protocol version |
| Protocol Revision | BACnet protocol revision |
| Max APDU Length Accepted | Maximum APDU size in bytes |
| Segmentation Supported | Segmentation capability |
| APDU Timeout | Per-request timeout in milliseconds |
| APDU Retries | Number of APDU retries |
| Database Revision | Configuration database revision counter |
| Last Restart Reason | Reason for last device restart |
| Backup and Restore State | Backup/restore operational state |
| Local Date | Device local date |
| Local Time | Device local time |
| UTC Offset | UTC offset in minutes |
| Daylight Savings | Daylight savings status |
| Profile Name | BACnet interoperability profile |
Severity mapping
| Finding | Severity |
|---|---|
| Device responds but no properties readable | High |
| Identifying properties readable unauthenticated | Critical |
Options
| Flag | Short | Default | Description |
|---|---|---|---|
--host <HOST> | -H | (required) | Target BACnet/IP device |
--port <PORT> | -p | 47808 | BACnet/IP UDP port |
--timeout-ms <MS> | - | 5000 | Per-request timeout in ms |
--output <FILE> | -o | - | Save result to a file |
--format <FORMAT> | -f | text | text or json |
--verbose | -v | - | Increase log verbosity |
Example
$ iottack bacnet info --host 192.168.1.50
Plugin name: bacnet/info
Execution time: 2.31 s
Status: pass
Date: 2025-11-05 00:00:00 UTC
18 device properties readable unauthenticated at 192.168.1.50:47808
Address: 192.168.1.50:47808
Device ID: 1001
Vendor ID: 16 (Siemens)
Max APDU: 1476
Object Identifier: Device:1001
Object Name: HVAC-Controller-01
System Status: 0
Vendor Name: Siemens
Model Name: PXC100.D
Firmware Revision: 2.4.1
Application Software Version: 3.1.0
Description: Building 7, HVAC Zone A
Location: Level 3, Plant Room
Protocol Version: 1
Protocol Revision: 14
Local Date: 2025-11-05
Local Time: 09:42:15.00
UTC Offset (min): -300