bacnet - device-properties
Enumerate all standard properties of the BACnet Device object.
Usage
iottack bacnet device-properties --host <HOST> [OPTIONS]
Description
Reads every standard ASHRAE 135 property of the Device object on the
target via unauthenticated ReadProperty requests. Properties that the
device does not support or restricts are shown as <not readable>.
The Device object is the root of a BACnet device’s information model. Its properties expose configuration, capability and operational state. Readable properties are reported as Critical findings.
Properties attempted
Required Device object properties, optional common properties, and operational flags:
- Object Identifier, Object Name, Object Type
- System Status, Vendor Name, Vendor Identifier, Model Name
- Firmware Revision, Application Software Version
- Protocol Version, Protocol Revision
- Protocol Services Supported, Protocol Object Types Supported
- Object List, Max APDU Length Accepted, Segmentation Supported
- APDU Timeout, Number of APDU Retries, Database Revision
- Description, Location, Local Date, Local Time, UTC Offset
- Daylight Savings Status, Profile Name
- Last Restart Reason, Backup and Restore State
- Out of Service, Event State, Status Flags
Severity mapping
| Finding | Severity |
|---|---|
| No Device properties readable | Info |
| Device properties readable unauthenticated | Critical |
Options
| Flag | Short | Default | Description |
|---|---|---|---|
--host <HOST> | -H | (required) | Target BACnet/IP device |
--port <PORT> | -p | 47808 | BACnet/IP UDP port |
--timeout-ms <MS> | - | 5000 | Per-request timeout in ms |
--output <FILE> | -o | - | Save result to a file |
--format <FORMAT> | -f | text | text or json |
--verbose | -v | - | Increase log verbosity |
Example
$ iottack bacnet device-properties --host 192.168.1.50
Plugin name: bacnet/device-properties
Execution time: 8.74 s
Status: pass
Date: 2025-10-06 00:00:00 UTC
24 of 31 Device properties readable unauthenticated at 192.168.1.50:47808
Object Identifier: Device:1001
Object Name: HVAC-Controller-01
Object Type: 8
System Status: 0
Vendor Name: Siemens
Vendor Identifier: 16
Model Name: PXC100.D
Firmware Revision: 2.4.1
Application Software Version: 3.1.0
Protocol Version: 1
Protocol Revision: 14
Protocol Services Supported: <binary/complex>
Protocol Object Types Supported: <binary/complex>
Max APDU Length Accepted: 1476
Segmentation Supported: 3
APDU Timeout (ms): 6000
Number of APDU Retries: 3
Database Revision: 42
Description: Building 7, HVAC Zone A
Location: Level 3, Plant Room
Local Date: 2025-11-06
Local Time: 09:42:15.00
UTC Offset (min): -300
Out of Service: false
...
Profile Name: <not readable>
Event State: <not readable>