Keyboard shortcuts

Press ← or → to navigate between chapters

Press S or / to search in the book

Press ? to show this help

Press Esc to hide this help

bacnet - object-list

Enumerate all BACnet objects on a device and read their present values unauthenticated.

Usage

iottack bacnet object-list --host <HOST> [OPTIONS]

Description

Implements the list_objects and list_objects_info recon operations from BACteria.

  1. Object list: reads the object-list property (prop 76) from the Device object to obtain every BACnet object instantiated on the device.
  2. Object names: reads the object-name property (prop 77) for each object.
  3. Present values: for data-point types (Analog-Input/Output/Value, Binary-Input/Output/Value, Multi-State-Input/Output/Value) the present-value property (prop 85) is read, exposing live sensor and actuator readings.

Note: Very large object lists (> ~200 objects) may exceed the 1024-byte APDU limit. Use --max-objects to cap enumeration and a dedicated BACnet client for exhaustive scans.

Severity mapping

FindingSeverity
Object list not readableInfo
Object list accessible unauthenticatedHigh
Data-point present values readableCritical

Options

FlagShortDefaultDescription
--host <HOST>-H(required)Target BACnet/IP device
--port <PORT>-p47808BACnet/IP UDP port
--timeout-ms <MS>-5000Per-request timeout in MS
--max-objects <N>-64Maximum number of objects to enumerate
--output <FILE>-o-Save result to a file
--format <FORMAT>-ftexttext or json
--verbose-v-Increase log verbosity

Example

$ iottack bacnet object-list --host 192.168.1.50

Plugin name:    bacnet/object-list
Execution time: 12.40 s
Status:         pass
Date:           2026-10-18 00:00:00 UTC

BACnet object list readable at 192.168.1.50:47808: 18 objects
  Device:0  name=HVAC-Controller
  Analog-Input:0  name=Supply-Air-Temp  present-value=22.1500
  Analog-Input:1  name=Return-Air-Temp  present-value=19.3200
  Binary-Output:0  name=Fan-Enable  present-value=1
  ...

3 process data-points readable unauthenticated at 192.168.1.50:47808
  Analog-Input:0 = 22.1500 (Supply-Air-Temp)
  Analog-Input:1 = 19.3200 (Return-Air-Temp)
  Binary-Output:0 = 1 (Fan-Enable)